G120 reported failure of F1910 communication message, how to shield this fault?

1. Is there any looseness of the DP connector wiring and is the DP cable shield grounded?
2, with or without line reactors, filters?
3. Are shielded cables or shielded 3+3 cables used?
As for the shielding failure, do not always want to shield when there is a failure, but to find a solution.
1, P2110 = 1910, P2101 = 1, can be shielded
  2, P2118[0]=1910, P2119[0]=3, can also be shielded
3, after shielding, if there is a disconnection, the inverter will continue to operate.

Siemens inverter repair