Siemens Drive Repair Center
Siemens Touch Screen PLC Center
Siemens touch screen repair center
Siemens CNC Repair Center
Siemens inverter repair
Contact method

Siemens inverter repair 

Siemens inverter repair

DC speed regulator 6RA70 reported fault F048

Publish Date 2016-11-03
1, F048 this fault is likely to be due to interference caused by false positives, I have encountered this situation.

I suggest you check it out:
1) whether the encoder signal cable shielded cable;
2) Is the signal cable shield well grounded?
3) No adapters are allowed in the signal cable.
2, in addition, you look at the value of the fault in parameter r949 -
and repair services: 24H service hotline: 158004

Fault value =:
1 - The encoder cable is faulty
2 - Damaged pulse encoder

         If the fault value is 1, the problem is mostly on the signal cable of the encoder, such as if the cable is not in good contact, etc.; if the fault value is 2, it is likely to be interference, or the encoder is not installed.

Siemens inverter repair
Siemens inverter repair center
SIEMENS/Siemens Inverter Repair Center/Maintenance Service: 24H Service Hotline: 15800462088
Siemens inverter repair center, provide home maintenance inspection and repair services: 24H service hotline: 15800462088






Siemens Drive Repair Center  |  Siemens Touch Screen PLC Center  |  Siemens touch screen repair center  |  Siemens CNC Repair Center  |  Siemens inverter repair  |  Contact method  |  Sitemap  |  Mobile Version
  简体版     繁體版     English

Powered by DIYTrade.com  Build your FREE website !
Find Best Price For China Products !