DC speed regulator 6RA70 reported fault F048

Publish Date 2016-11-03
1, F048 this fault is likely to be due to interference caused by false positives, I have encountered this situation.

I suggest you check it out:
1) whether the encoder signal cable shielded cable;
2) Is the signal cable shield well grounded?
3) No adapters are allowed in the signal cable.
2, in addition, you look at the value of the fault in parameter r949 -
and repair services: 24H service hotline: 158004

Fault value =:
1 - The encoder cable is faulty
2 - Damaged pulse encoder

         If the fault value is 1, the problem is mostly on the signal cable of the encoder, such as if the cable is not in good contact, etc.; if the fault value is 2, it is likely to be interference, or the encoder is not installed.