Siemens Drive Repair Center
Siemens Touch Screen PLC Center
Siemens touch screen repair center
Siemens CNC Repair Center
Siemens inverter repair
Contact method

Siemens inverter repair 

Siemens inverter repair

Can the G120 CU240E-2 analog output be a voltage?

Publish Date 2017-08-21
Description: Sets the type of analog output.
P0776[x] = 1 corresponds to the voltage output (p0774, p0778, p0780 are displayed in V units).
P0776[x] = 0, 2 corresponds to the current output (p0774, p0778, p0780 displayed in mA).
Value: 0: Current output (0 mA ... +20 mA)
1: Voltage output (0 V ... +10 V)
2: Current output (+4 mA ... +20 mA)
Index: [0] = AO0 (Kl 12/13)
[1] = AO1 (Kl 26/27)
Note: When p0776 is modified, the parameters of the scaling curve (p0777, p0778, p0779, p0780) become the following default values:
When p0776 = 0, p0777 = 0.0 %, p0778 = 0.0 mA, p0779 = 100.0 %, p0780 = 20.0 mA.
When p0776 = 1, p0777 = 0.0 %, p0778 = 0.0 V, p0779 = 100.0 %, p0780 = 10.0 V.
When p0776 = 2, p0777 = 0.0 %, p0778 = 4.0 mA, p0779 = 100.0 %, p0780 = 20.0 mA.
standard answer:
Yes, the analog output type can be changed by setting parameter P776.


Siemens inverter repair
Siemens inverter repair center
SIEMENS/Siemens Inverter Repair Center/Maintenance Service: 24H Service Hotline: 15800462088
Siemens inverter repair center, provide home maintenance inspection and repair services: 24H service hotline: 15800462088






Siemens Drive Repair Center  |  Siemens Touch Screen PLC Center  |  Siemens touch screen repair center  |  Siemens CNC Repair Center  |  Siemens inverter repair  |  Contact method  |  Sitemap  |  Mobile Version
  简体版     繁體版     English

Powered by DIYTrade.com  Build your FREE website !
Find Best Price For China Products !