Can the G120 CU240E-2 analog output be a voltage?
|
|
Description: Sets the type of analog output. P0776[x] = 1 corresponds to the voltage output (p0774, p0778, p0780 are displayed in V units). P0776[x] = 0, 2 corresponds to the current output (p0774, p0778, p0780 displayed in mA). Value: 0: Current output (0 mA ... +20 mA) 1: Voltage output (0 V ... +10 V) 2: Current output (+4 mA ... +20 mA) Index: [0] = AO0 (Kl 12/13) [1] = AO1 (Kl 26/27) Note: When p0776 is modified, the parameters of the scaling curve (p0777, p0778, p0779, p0780) become the following default values: When p0776 = 0, p0777 = 0.0 %, p0778 = 0.0 mA, p0779 = 100.0 %, p0780 = 20.0 mA. When p0776 = 1, p0777 = 0.0 %, p0778 = 0.0 V, p0779 = 100.0 %, p0780 = 10.0 V. When p0776 = 2, p0777 = 0.0 %, p0778 = 4.0 mA, p0779 = 100.0 %, p0780 = 20.0 mA. standard answer: Yes, the analog output type can be changed by setting parameter P776.