Can the G120 CU240E-2 analog output be a voltage?

Publish Date 2017-08-21
Description: Sets the type of analog output.
P0776[x] = 1 corresponds to the voltage output (p0774, p0778, p0780 are displayed in V units).
P0776[x] = 0, 2 corresponds to the current output (p0774, p0778, p0780 displayed in mA).
Value: 0: Current output (0 mA ... +20 mA)
1: Voltage output (0 V ... +10 V)
2: Current output (+4 mA ... +20 mA)
Index: [0] = AO0 (Kl 12/13)
[1] = AO1 (Kl 26/27)
Note: When p0776 is modified, the parameters of the scaling curve (p0777, p0778, p0779, p0780) become the following default values:
When p0776 = 0, p0777 = 0.0 %, p0778 = 0.0 mA, p0779 = 100.0 %, p0780 = 20.0 mA.
When p0776 = 1, p0777 = 0.0 %, p0778 = 0.0 V, p0779 = 100.0 %, p0780 = 10.0 V.
When p0776 = 2, p0777 = 0.0 %, p0778 = 4.0 mA, p0779 = 100.0 %, p0780 = 20.0 mA.
standard answer:
Yes, the analog output type can be changed by setting parameter P776.


Siemens inverter repair
Siemens inverter repair center
SIEMENS/Siemens Inverter Repair Center/Maintenance Service: 24H Service Hotline: 15800462088
Siemens inverter repair center, provide home maintenance inspection and repair services: 24H service hotline: 15800462088






Siemens Drive Repair Center  |  Siemens Touch Screen PLC Center  |  Siemens touch screen repair center  |  Siemens CNC Repair Center  |  Siemens inverter repair  |  Contact method  |  Sitemap  |  Mobile Version
  简体版     繁體版     English

Powered by DIYTrade.com  Build your FREE website !