G120 reported failure of F1910 communication message, how to shield this fault?
|
|
1. Is there any looseness of the DP connector wiring and is the DP cable shield grounded? 2, with or without line reactors, filters? 3. Are shielded cables or shielded 3+3 cables used? As for the shielding failure, do not always want to shield when there is a failure, but to find a solution. 1, P2110 = 1910, P2101 = 1, can be shielded 2, P2118[0]=1910, P2119[0]=3, can also be shielded 3, after shielding, if there is a disconnection, the inverter will continue to operate.